How To use more than 500 Bytes with Rockwell Studio 5000?

31 May 2023

This article, it is explained how to use more than 500 Bytes with the Ethernet/IP gateway. 

 

APPLICABLE PRODUCTS

  • ABC4014-A
  • ABC4012
  • ABC4011
  • ABC4091
  • ABC4090
  • ABC3090
  • ABC3007

PROBLEM

It is not possible to assign more than 500 Bytes in Rockwell Studio 5000. 

 

ANSWER

 

The reason that it is not possible is simply Rockwell doesn't support large forward open service with Class 1 connections. 

To be able to assign more than 500 bytes, it is necessary to use a Class 3 connection as it is explained in the video below. 

 

How To - Set Up a EtherNet/IP Class 3 Connection in Studio 5000