What are the Assembly Object Instances for Anybus Ethernet/IP device?

19 Sep 2022

This article shows the Standard I/O Assembly Object Connection Points for Anybus Ethernet/IP devices.

 

APPLICABLE PRODUCTS

Anybus Ethernet/IP devices

 

QUESTION

What are the assembly instances to read data from an Anybus Ethernet/IP device?

 

 

ANSWER

Anybus Ethernet/IP devices will typically use Assembly object (0x04). The Input instance 100 ( 0x64) and Output Instance 150 (0x96).   With data in the default attribute 3 (0x03).  For additional Info we recommended referring to the Applicable Network Guides for the device.  These can be found in the Files and Documents pages of the device and those can be accessed though our Anybus.com support page.