How many slave devices an Ewon Flexy can poll

27 Sep 2022
This document will give you the maximum number of devices that can be polled by the Ewon Flexy per IOServer/Communication protocol

 

APPLICABLE PRODUCTS

Ewon : Flexy

 

IN THIS ARTICLE

 

Modbus RTU (Modbus IOserver)

By default, a Modbus RS485 network supports 32 Slaves.
But if the Modbus Slave devices have a high input impedance (like the one used in Ewon), then this limit can be extended to 254 devices .
Pay attention that the network must be terminated and polarized to achieve such a performance.

Modbus TCP (Modbus IOserver)

In Modbus TCP, you can poll up to 32 devices

Ethernet IP (DF1/ABLogix IOservers)

In Ethernet IP, you can poll up to 16 devices

Siemens MPI (S3&400 IOserver)

In MPI, you can poll up to 127 devices

Siemens ISOTCP (S3&400 IOserver)

In ISOTCP, you can poll up to 32 devices