How do the PROFINET reset modes relate to the ones in the Anybus CompactCom 40 for PROFINET?

07 Dec 2022

This article goes about which PROFINET reset modes belong to which codes that are sent via the Application Object's (0xFF) Reset command to the host application.

 

APPLICABLE PRODUCTS

Anybus CompactCom 40 for PROFINET

 

QUESTION

How do the PROFINET reset modes relate to the ones in the Anybus CompactCom 40 for PROFINET?

 

 

ANSWER

In the Anybus CompactCom 40 for PROFINET, there is the following assignment between the PROFINET reset modes and the codes that are transferred to the Application Object 0xFF via the reset command.

PROFINET Reset Mode CmdExt[1] of Application Object's Reset command
2

(Reset communication parameter)

[station name = "",
IP = 0.0.0.0,
DHCP (if available),
all PDev parameters (topology, etc.),
SNMP writeable OIDs]

n/a (no message is sent towards the Application Object)

8 0x02 (Power-on + Factory default reset)