User Interface
Anybus' second-generation gateways offer world-leading usability thanks to the intuitive Graphical User Interface (GUI). You can even try the user Interface before you buy!
A protocol converter that connects serial devices to Modbus TCP control systems
Item number ABC3028-A
The Anybus Communicator Serial Master to Modbus TCP enables you to connect any RS-232/485 device or equipment to Modbus TCP control systems. Anybus Communicators ensure reliable, secure, and high-speed data transfers between different industrial networks. Thanks to our intuitive web-based user interface, they're also incredibly easy to use.
Push Buttons
Factory reset
Connectors / Input / Output
1x 7-pin, 5.08 Phoenix plug connector, 2xRJ45, RJ45 Config port
Contains Battery
No
CE
Yes
UL
Yes
UL Information
E214107: Ord.Loc UL 61010-1, CSA C22.2 No. 61010-1, UL 61010-2-201, CSA C22.2 No. 61010-2-201
ATEX
No
KC
Yes
EMC
Yes
Environment
EN 55016-2-3 Class A, EN 55032 Class A, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Waste Certification (WEEE)
Yes
WEEE Category
IT and telecommunications equipment
Protection Class IP
IP20
Predecessor
AB7028-C, AB7028-C-5PACK
Item Number
ABC3028-A
Export Control Classification Number (ECCN)
5A991.b.1
Dual Usage
No
Country of Origin
Sweden
Brand
Anybus
HS Code
8517620000
Model Code
40-SER-ETH-B
Net Width (mm)
27 mm
Net Height (mm)
144 mm
Net Depth (mm)
98 mm
Net Weight (g)
150 g
Mounting
DIN-rail (EN 50022 standard)
Current Consumption Type Value at Vcc Nom (mA)
90mA @ 24V DC (2.2W)
Current Consumption Max value at Vcc nom (mA)
125mA @24V DC (3W)
Input Voltage (V)
12-30V DC
Power Connector
3-pin, 5.08 Phoenix plug connector
Reverse Polarity Protection
Yes
Short Circuit Protection
Yes
Isolation
TRUE
Operating Temperature °C Min
-25 °C
Operating Temperature °C Max
70 °C
Storage Temperature °C Min
-40 °C
Storage Temperature °C Max
85 °C
Housing Materials
PC ABS, UL 94 VO
Packaging Material
Cardboard
Warranty (years)
5
Packed Weight (g)
185 g
Packed Depth (mm)
115 mm
Packed Height (mm)
170 mm
Packed Width (mm)
35 mm
Modbus-TCP Mode
Slave / Server
Modbus-TCP Supported Functionality
Modbus specification V1.1b3; 4 connections; Daisy chaining
Modbus-TCP Bandwidth
10/100 Mbit/s
Modbus-TCP Input Data Size
1500 bytes
Modbus-TCP Output Data Size
1500 bytes
Modbus-TCP Functions Supported
1, 2, 3, 4, 5, 6, 15, 16, 23, 43/14
Modbus-RTU Mode
Client / Master
Modbus-RTU Supported Functionality
RS-232; RS485; Standard Modbus RTU Master; Custom Request / Responce commands; Custom Produce / Consume transactions; Trigger initated transactions; 7 or 8 data bit; None, Odd, Even Parity; 1 or 2 stop bit; Clear/Freeze
Modbus-RTU Baud Rate
1200,1800,2400,4800,7200,9600,14400,19200,35700,38400,57600,115200,128000 bit/s
Modbus-RTU Input Data Size
1500 bytes
Modbus-RTU Output Data Size
1500 bytes
Modbus-RTU Functions Supported
1, 2, 3, 4, 5, 6, 7, 8, 11, 12, 15, 16, 17, 20, 21, 22, 24
Baud Rate
1200,1800,2400,4800,7200,9600,14400,19200,35700,38400,57600,115200,128000 bit/s
Max Stations
31
Connector
1x 7-pin, 5.08 Phoenix plug connector
Max Nodes
31
Training from HMS Academy reduces the total cost and time of your project and gives improved quality and efficiency of the solution.
HMS offers trainings related to products, technologies and more. This could be in the form of an onsite training, online training or by running one of our E-learning sessions.
Technical Services from HMS helps customers with any type of assistance needed in addition to the products bought from HMS. The Technical Services page offers a list of all services we provide.
The services are provided by HMS’ global team of skilled and experienced engineers who work together with you, providing various services.
Typical activities are project planning, setting up evaluation demos, creating and validating product configurations, providing guidance during field trials, and more.
Technical Services from HMS helps customers with any type of assistance needed in addition to the products bought from HMS. The Technical Services page offers a list of all services we provide.
The services are provided by HMS’ global team of skilled and experienced engineers who work together with you, providing various services.
Typical activities are project planning, setting up evaluation demos, creating and validating product configurations, providing guidance during field trials, and more.