This article describes common problems when using the DeviceNet Master Gateway.
APPLICABLE PRODUCTS
AB7630,AB7647,AB7916,AB7816,AB7817,AB7663
QUESTION
When scanning a DeviceNet network in Anybus Configuration Manager - DeviceNet tool, no devices were scanned.
ANSWER
1. Use DeviceNet specific cables.
2. Check all DeviceNet devices have the same baud rate. The gateway uses switch 1 and switch 2 to set the baud rate.
3. Every device has a unique address. The gateway uses switch 3~switch 8 to set the Mac ID.
4. DeviceNet interface requires 24V bus power.
5. Both ends of the network need 120Ω terminating resistor.